SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
308
3.49 Momentary Power Failure during Test Operation
Applicable
Models
All outdoor unit models
Error Code
L2
Method of Error
Detection
Momentary power failure is detected by the PCB.
Error Decision
Conditions
Judgment is made by AC power frequency detection circuit on the outdoor unit main PCB.
Supposed
Causes
Defective wiring
Defective outdoor unit main PCB
Troubleshooting
Error
rec
u
rs after
t
u
rning OFF the power
and ON again.
Any
disconnection
of connectors, loose
contact or wiring
disconnection in the
transmission wirings to the
o
u
tdoor
u
nit main
PCB?
NO
YES
YES
NO
Temporary pro
b
lem
Correct any fa
u
lt.
Replace the o
u
tdoor
u
nit
main PCB (A1P).
Caution
Be s
u
re to t
u
rn off the power switch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...