Field Settings for Outdoor Unit
SiUS342004EB
203
Part 5 Field Settings and Test Operation
In case of heating operation the condense temperature is allowed to go up to 115°F (46°C) on
temporary base depending on the situation.
When the request from the indoor units becomes more moderate, the system will eventually go to
the steady state condition which is defined by the operation method above.
To activate the quick comfort setting under cooling operation, change field setting [2-81] to 2.
This setting is used in conjunction with settings [2-8].
To activate the quick comfort setting under heating operation, change field setting [2-82] to 2.
This setting is used in conjunction with setting [2-9].
• Mild
Overshoot (during heating operation) or undershoot (during cooling operation) is allowed compared
to the requested refrigerant temperature, in order to achieve the required room temperature very
fast. The overshoot is not allowed from the start up moment. The start up occurs under the
condition which is defined by the operation mode above.
In case of cooling operation the evaporating temperature is allowed to go down to 43°F (6°C) on
temporary base depending on the situation.
In case of heating operation the condense temperature is allowed to go up to 115°F (46°C) on
temporary base depending on the situation.
When the request from the indoor units becomes more moderate, the system will eventually go to
the steady state condition which is defined by the operation method above.
The start up condition is different from the powerful and quick comfort setting.
To activate the mild comfort setting under cooling operation, change field setting [2-81] to 1.
This setting is used in conjunction with settings [2-8].
To activate the mild comfort setting under heating operation, change field setting [2-82] to 1.
This setting is used in conjunction with setting [2-9].
• Eco
The original refrigerant temperature target, which is defined by the operation method (see above) is
kept without any correction, unless for protection control.
To activate the eco comfort setting under cooling operation, change field setting [2-81] to 0. This
setting is used in conjunction with setting [2-8].
To activate the eco comfort setting under heating operation, change field setting [2-82] to 0. This
setting is used in conjunction with setting [2-9].
No matter which control is selected, variations on the behavior of the system are still possible due
to protection controls to keep the unit operating under reliable conditions. The intentional target,
however, is fixed and will used to obtain the best balance between energy consumption and
comfort, depending on the application type.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...