Protection Control
SiUS342004EB
99
Part 4 Functions and Control
Radiation Fin
Temperature
Control
Perform the following control of integrated as well as multi units for each compressor.
Condition
All outdoor units
A
more than 90°C (194°F)
B
less than 87°C (188.6°F)
C
more than 95°C (203°F)
Normal control
Fin temperature standby
Reduce compressor capacity
A
B
When occurring 4 times within 60
minutes, the error code
L4
is output.
C