SiUS342004EB
Special Control
Part 4 Functions and Control
100
7. Special Control
7.1 Pump Down Residual Operation
If the liquid refrigerant stays in the evaporator at the startup of a compressor, this liquid refrigerant
enters the compressor, thus resulting in diluted oil in the compressor and then degraded lubrication
performance.
Consequently, in order to recover the refrigerant in the evaporator while the compressor stops, the
pump down residual operation is conducted.
Pc: High pressure sensor detection value
Pe: Low pressure sensor detection value
Ta: Outdoor air temperature
Te: Low pressure equivalent saturation temperature
DSH: Discharge pipe superheating degree
RXYQ72XA, RXYQ72XB
7.2 Oil Return Operation
In order to prevent the compressor from running out of oil, the oil return operation is conducted to
recover oil that has flowed out from the compressor to the system side.
Tc : High pressure equivalent saturation temperature
Te : Low pressure equivalent saturation temperature
TsA: Suction pipe temperature detected by thermistor R3T
Part name
Electric symbol
Function of functional part
Normal cooling
Normal heating
Compressor
M1C
24 rps/37 rps
24 rps/37 rps
Fan motor
M1F, M2F
For heat exchanger mode
For heat exchanger mode
Electronic expansion valve
(Heat exchanger upper)
Y1E
Same as normal control
Same as normal control
Electronic expansion valve
(Heat exchanger lower)
Y3E
Electronic expansion valve
(Subcooling heat exchanger)
Y2E
0 pulse
0 pulse
Electric expansion valve
(Subcooling injection)
Y4E
760 pulse
760 pulse
Electronic expansion valve
(Refrigerant cooling)
Y5E
Same as normal control
Same as normal control
Electronic expansion valve
(Receiver gas purge)
Y7E
Open slightly
Open slightly
Solenoid valve
(Oil separator oil return)
Y1S
ON
ON
Solenoid valve (Hot gas bypass)
Y2S
OFF
OFF
Solenoid valve (Liquid shutoff)
Y3S
ON
ON
Four way valve (HP/LP gas pipe)
Y4S
Hold
Hold
Four way valve
(Heat exchanger lower)
Y5S
Hold
Hold
Four way valve
(Heat exchanger upper)
Y6S
Hold
Hold
Solenoid valve
(Accumulator oil return)
Y7S
ON
ON
Ending condition
A lapse of 5 min
u
tes
Master
u
nit HTdi > 118
°
C (244.4°F)
Pc_max > 2.94 MPa (426 psi)
OR
A lapse of 3 min
u
tes
Pe_min < 0.19 MPa (27.6 psi)
Ta_min – Te_max > 8
°
C (14°F)
HTdi_max > 118
°
C (244.4°F)
OR
&
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...