SiUS342004EB
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
176
[1-10]:
shows the total number of connected indoor units.
It can be convenient to check if the total number of indoor units which are installed
match the total number of indoor units which are recognized by the system. In case
there is a mismatch, it is advised to check the communication wiring path between
outdoor and indoor units (F1/F2 communication line).
[1-13]:
shows the total number of connected outdoor units.
It can be convenient to check if the total number of outdoor units which are installed
matches the total number of outdoor units which are recognized by the system. In
case there is a mismatch, It is advised to check the communication wiring path
between outdoor and outdoor units.
[1-17]:
shows the latest error code.
[1-18]:
shows the 2nd last error code.
[1-19]:
shows the 3rd last error code.
When the latest error codes were reset by accident on an indoor unit user interface,
they can be checked again through this monitoring settings.
[1-40]:
shows the current cooling comfort setting.
[1-41]:
shows the current heating comfort setting.
[1-42]:
shows the current high pressure sensor value (psi).
[1-43]:
shows the current low pressure sensor value (psi).
[1-44]:
shows the current compressor speed (Hz).
[1-45]:
shows the current EEV (heat exchanger upper) opening (pulse divided by 10).
[1-46]:
shows the current EEV (heat exchanger lower) opening (pulse divided by 10).
[1-47]:
shows the current discharge thermistor value (°F).
[1-49]:
shows the current compressor body thermistor value (°F).
[1-50]:
shows the current outdoor air thermistor value (°F).
[1-51]:
shows the current compressor suction thermistor value (°F).
[1-52]:
shows the current subcooling gas thermistor value (°F).
[1-53]:
shows the current heat exchanger gas (upper) thermistor value (°F).
[1-54]:
shows the current heat exchanger gas (lower) thermistor value (°F).
[1-55]:
shows the current deicer thermistor value (°F).
[1-56]:
shows the compressor run time (hour divided by 100).
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...