Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
194
2.5.5 Heat Pump Lockout
New control logic to provide more application options for cold climates.
Outside temperature can now be measured directly from the outdoor unit coil sensor.
This field setting can switch automatically to emergency heat if there is a system fault.
Item
Description
Min
Max
Increments
Heat pump
lockout
temperature
Below this temperature, heat pump is
locked out.
–15°F
(–26.1°C)
(default)
50°F
(10°C)
5°F
(2.8°C)
Heat pump
lockout release
differential
When the outdoor air temperature is
recovered by this temperature, heat
pump is resumed.
5°F, 10°F (default), 15°F
(2.8°C, 5.6°C (default), 8.3°C)
[2-16]:
Auxiliary heater setting (Type I)
Value
[2-16]
Auxiliary heater
0 (default)
OFF
1
ON
[2-37]:
Auxiliary heater setting (Type II)
Value
[2-37]
Controlling mode
0 (default)
OFF
1
Mode 1
2
Mode 2
3
Mode 3
4
Mode 4
5
Mode 5
6
Mode 6
Type
Description
Actions
Field
setting
Shorted
between
Heating thermostat
ON
Heating thermostat
OFF
Auxiliary
heater
Indoor fan
Auxiliary
heater
Indoor fan
l
—
Heat pump heating is
always locked out
2-16: ON
—
ON
ON (H/L)
OFF
LL
ll
Mode 1
Lockout is controlled by
ABC terminals
2-37:
Mode 1
A-C
ON
ON (H/L)
OFF
LL
B-C
OFF
Mode 2
(for a heater which
does not need airflow)
2-37:
Mode 2
A-C
LL
LL
B-C
OFF
Mode 3
Lockout is controlled by
the outdoor air
temperature and
setpoint which is
configured by the field
setting [2-78] and [2-79]
2-37:
Mode 3
Same as 2-37: Mode 1, A-C shorted
Mode 4
2-37:
Mode 4
Same as 2-37: Mode 1, B-C shorted
Mode 5
2-37:
Mode 5
Same as 2-37: Mode 2, A-C shorted
Mode 6
2-37:
Mode 6
Same as 2-37: Mode 2, B-C shorted
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...