Troubleshooting by Error Code
SiUS342004EB
343
Part 6 Service Diagnosis
NO
YES
YES
YES
NO
NO
Replace the outdoor unit main
PCB (A1P).
Check for the model of outdoor
unit.
Make setting again, and then
reset the power supply.
Replace the spare PCB.
NO
YES
Replace the outdoor unit main
PCB (A1P).
Was the
outdoor unit
main PCB replaced with
a spare PCB?
A
different model
of outdoor unit is
connected.
Diagnosis Flowchart-3
Error code
Sub code
UA-
20
Multi connection?
Was proper setting
of spare PCB
made?
Diagnosis Flowchart-4
NO
Disconnect residential indoor units
from the system.
Are all
indoor units for
VRV
? (no residential
indoor units)
Error code
Sub code
UA-
2
1
YES
Replace the outdoor unit main PCB
(A1P).