SiUS342004EB
Symptom-based Troubleshooting
Part 6 Service Diagnosis
212
1.2 Low-Temperature Hydrobox Overall
Regarding the symptom-based troubleshooting of the low-temperature hydrobox (HXY-TA), refer to
the service manual SiUS392016EA.
1.3 With Gas Furnace
1.4 Gas Furnace Lockout Reset
Furnace lockout is characterized by a non-functioning furnace (circulator blower may be running
continuously) providing a diagnostic LED code located on the furnace board.
Lockout results when a furnace control detects abnormal conditions. If the furnace is in "lockout",
the following methods can be used to clear the error.
a. Turn the remote controller OFF to clear the error. If the error is not cleared, proceed to next step.
b. Heat pump lockout conditions are met.
c. Set the setting temperature to maximum, then turn the remote controller ON.
d. Turn the remote controller OFF.
e. Turn the remote controller ON after around 15 seconds from procedure d.
The procedures c, d, and e will not work during certain outdoor unit operations, i.e. defrost, startup,
compressor stop, service mode etc.
If the LED of the
ON/OFF
button is flashing when you turn the remote controller ON, you cannot
clear the error with the method above. In that case, the error must be cleared using the gas
furnace. Refer to the gas furnace operation manual for more details.
Symptom
Supposed Cause
1
The gas furnace does not start operation.
The gas furnace does not start operation while the compressor is
during operation or under stop-control, or right after defrost IN or
defrost OUT. Wait until the operation becomes stable.
2
Operation does not switch from heat pump to gas furnace in
spite of low room temperature. Operation does not switch from
gas furnace to heat pump even though the room temperature is
nearing the set temperature.
This function is performed only with outdoor units which support
automatic switching between gas furnace and heat pump
interlocking with room temperature.
Some models are enabled to support automatic switching
between gas furnace and heat pump interlocking with outdoor air
temperature by setting heat pump lockout on an outdoor unit
side. However, the compressor stops while gas furnace is during
operation.
3
AA-03
(Gas furnace abnormality) is indicated on the remote
controller while no error is indicated on the PCB of the gas
furnace.
In some cases of gas furnace abnormality, error indication on the
remote controller is retained even after the abnormality is
removed. Execute combustion heating operation once or reset
the power source.
4
The airflow rate indication on the remote controller is not
consistent with the actual airflow rate of the indoor unit.
The airflow rate of the indoor unit during gas furnace combustion
heating depends on the intensity of combustion.
Therefore, the airflow rate of the indoor unit does not reflect the
airflow setting of the remote controller.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...