Symptom-based Troubleshooting
SiUS342004EB
211
Part 6 Service Diagnosis
11 The system
produces sounds.
Indoor unit
Immediately after turning ON
the power supply, indoor unit
produces ringing sounds.
These are operating sounds of the
electronic expansion valve of the
indoor unit.
Normal operation.
This sound becomes low after a
lapse of approximately one minute.
Indoor and outdoor units
Hissing sounds are
continuously produced while in
cooling or defrost operation.
These sounds are produced from gas
(refrigerant) flowing respectively
through the indoor and outdoor units.
Normal operation.
Indoor and outdoor units
Hissing sounds are produced
immediately after the startup or
stop of the system, or the
startup or stop of defrost
operation.
These sounds are produced when
the gas (refrigerant) stops or changes
flowing.
Normal operation.
Indoor unit
Faint sounds are continuously
produced while in cooling
operation or after stopping the
operation.
These sounds are produced from the
drain discharge device in operation.
Normal operation.
Indoor unit
Creaking sounds are produced
while in heating operation or
after stopping the operation.
These sounds are produced from
resin parts expanding and
contracting with temperature
changes.
Normal operation.
Indoor unit
Sounds like trickling or the like
are produced from indoor units
in the stopped state.
On
VRV
systems, these sounds are
produced when other indoor units in
operation. The reason is that the
system runs in order to prevent oil or
refrigerant from dwelling.
Normal operation.
Outdoor unit
Pitch of operating sounds
changes.
The reason is that the compressor
changes the operating frequency.
Normal operation.
12 Dust comes out
from the system.
Dust comes out from the
system when it restarts after
the stop for an extended period
of time.
Dust, which has deposited on the
inside of indoor unit, is blown out
from the system.
Normal operation.
13 Odors come out
from the system.
In operation
Odors of room, cigarettes or else
adsorbed to the inside of indoor unit
are blown out.
The inside of the indoor unit should
be cleaned.
14 Outdoor fan does
not rotate.
In operation
The reason is that fan revolutions are
controlled to put the operation to the
optimum state.
Normal operation.
15 LCD display
88
or
Checking the
connection.
Please stand by.
appears on the
remote controller.
Immediately after turning ON
the power supply
The reason is that the system is
checking to be sure the remote
controller is normal.
Normal operation.
This code is displayed for a period of
approximately one minute at
maximum.
16 The outdoor unit
compressor or
the outdoor fan
does not stop.
After stopping operation
It stops in order to prevent oil or
refrigerant from dwelling.
Normal operation.
It stops after a lapse of approximately
5 to 10 minutes.
17 The outdoor gets
hot.
While stopping operation
The reason is that the compressor is
warmed up to provide smooth startup
of the system.
Normal operation.
18 Hot air comes out
from the system
even though it
stops.
Hot air is felt while the system
stops.
On
VRV
systems, small quantity of
refrigerant is fed to indoor units in the
stopped state when other indoor units
are in operation.
Normal operation.
Symptom
Supposed Cause
Countermeasure
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...