Troubleshooting by Error Code
SiUS342004EB
275
Part 6 Service Diagnosis
3.29 Infrared Presence/Floor Sensor Error
Applicable
Models
FXFQ-AA, FXFQ-T, FXZQ-TA, FXZQ-TB, FXUQ-P, FXUQ-PA
Error Code
CE
Method of Error
Detection
The contents of a failure vary with the detailed error code. Check the code and proceed with the
flowchart.
Error Decision
Conditions
Error is detected based on sensor output signals
Supposed
Causes
Defective or disconnected infrared presence sensor connector:
CE-01
Defective infrared floor sensor (Temperature compensation circuit disconnection):
CE-02
Defective infrared floor sensor (Temperature compensation short circuit):
CE-03
Defective infrared floor sensor element:
CE-04
Troubleshooting
See diagnosis procedure 1.
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
Error code
CE-01
See diagnosis procedure 2.
Error code
CE-02
See diagnosis procedure 3.
Error code
CE-03
See diagnosis procedure 4.
Error code
CE-04
Error type varies according
to error code. Check the
error code and take the
follo
w
ing steps.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...