Protection Control
SiUS342004EB
95
Part 4 Functions and Control
Heating
Pc
<
3.17 MPa
(460 psi)
Pc
<
3.22 MPa
(467 psi)
Pc
>
3.39 MPa
(492 psi)
Pc
>
3.31 MPa
(4
8
0 psi)
Pc
>
3.72 MPa
(540 psi)
N
ormal control
9-step do
w
n
All units
Compressor step: 1
3-step up
Current step
maintained
High pressure standby
(2 times
w
ithin 40 minutes)
Pc: High pressure sensor
detection value for master
unit
Abnormal stop
(
E3
is displayed)
Pc
>
3.31 MPa
(4
8
0 psi)
After 10
seconds
After 10
seconds
After 15
seconds
High pressure s
w
itch (4.0 MPa
(5
8
0 psi)
) is activated