SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
342
Note(s)
1. Refer to page 347.
NO
YES
YES
The
number of indoor
units connected to the
same system is less
than 64.
Incorrect
electric heater
capacity setting
troubleshooting (
1)
checked?
Replace the outdoor unit main
PCB (A1P).
Replace the outdoor unit main
PCB (A1P).
Refer to Incorrect electric heater
capacity setting troubleshooting.
(
1)
Excess indoor units are
connected.
Check for the connection to
connect the proper number of
indoor units.
NO
Diagnosis Flowchart-1
UA-17
Error code
Sub code
NO
YES
Is the
model of indoor
unit FXTQ-TA or
FXTQ-TB?
NO
YES
Check if the
refrigerant type of the
outdoor unit corresponds to
that of the indoor
unit.
Replace the outdoor unit main
PCB (A1P).
Match the refrigerant types of the
outdoor unit and the indoor unit.
Diagnosis Flowchart-2
Error code
Sub code
UA-18
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...