SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
226
L8 - 03
Compressor M1C overcurrent (Master)
Refer to the
L8
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
L8 - 06
Compressor M1C overcurrent (Slave 1)
L8 - 07
Compressor M1C overcurrent (Slave 2)
L9 - 01
Compressor M1C startup error (Master)
Refer to the
L9
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
L9 - 05
Compressor M1C startup error (Slave 1)
L9 - 06
Compressor M1C startup error (Slave 2)
L9 - 13
Inverter output open phase (Master)
L9 - 14
Inverter output open phase (Slave 1)
L9 - 15
Inverter output open phase (Slave 2)
LC - 14
Transmission error (Between outdoor units, inverter PCB)
(Master)
Refer to the
LC
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
LC - 15
Transmission error (Between outdoor units, inverter PCB)
(Slave 1)
LC - 16
Transmission error (Between outdoor units, inverter PCB)
(Slave 2)
LC - 19
Transmission error (Between outdoor units, fan PCB)
(Master): M1F
LC - 20
Transmission error (Between outdoor units, fan PCB)
(Slave 1): M1F
LC - 21
Transmission error (Between outdoor units, fan PCB)
(Slave 2): M1F
LC - 24
Transmission error (Between outdoor units, fan PCB)
(Master): M2F
LC - 25
Transmission error (Between outdoor units, fan PCB)
(Slave 1): M2F
LC - 26
Transmission error (Between outdoor units, fan PCB)
(Slave 2): M2F
LC - 33
Transmission error (Between outdoor units, sub PCB)
(Master)
LC - 34
Transmission error (Between outdoor units, sub PCB)
(Slave 1)
LC - 35
Transmission error (Between outdoor units, sub PCB)
(Slave 2)
P1 - 01
Inverter 1 power supply unbalanced voltage (Master)
Refer to the
P1
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
P1 - 02
Inverter 1 power supply unbalanced voltage (Slave 1)
P1 - 03
Inverter 1 power supply unbalanced voltage (Slave 2)
P4 - 02
Defective fan M1F fin sensor (Master)
Refer to the
P4
flowchart and make a diagnosis of the
relevant sensor based on the Error code shown to the left.
P4 - 03
Defective fan M2F fin sensor (Master)
P4 - 09
Defective inverter diode bridge fin sensor (Master)
P4 - 10
Defective inverter diode bridge fin sensor (Slave 1)
P4 - 11
Defective inverter diode bridge fin sensor (Slave 2)
P4 - 15
Defective fan M1F fin sensor (Slave 1)
P4 - 16
Defective fan M2F fin sensor (Slave 1)
P4 - 17
Defective fan M1F fin sensor (Slave 2)
P4 - 18
Defective fan M2F fin sensor (Slave 2)
PJ - 04
Incorrect type of inverter PCB (Master)
Refer to the
PJ
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
PJ - 05
Incorrect type of inverter PCB (Slave 1)
PJ - 06
Incorrect type of inverter PCB (Slave 2)
PJ - 09
Incorrect type of fan PCB (Master): M1F
PJ - 10
Incorrect type of fan PCB (Master): M2F
PJ - 15
Incorrect type of fan PCB (Slave 1): M1F
PJ - 16
Incorrect type of fan PCB (Slave 2): M1F
PJ - 17
Incorrect type of fan PCB (Slave 1): M2F
PJ - 18
Incorrect type of fan PCB (Slave 2): M2F
Error code
Troubleshooting
Error Description
Diagnosis
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...