3.21 Blower Motor Communication Error
Applicable
Models
FXTQ-TA, FXTQ-TB
Error Code
C1-07
Outline
Error is issued if transmission abnormalities occur between indoor unit and fan motor.
Error Decision
Conditions
If the response message from the fan motor is an abnormal message, and determined as such by
the indoor unit, the indoor unit will execute a retry.
If everything fails for 5 seconds, it is deemed to be a transmission abnormality.
Error Reset
Conditions
If the indoor unit receives even a single normal response message from the fan motor, the error will
be cleared.
Supposed
Causes
Incorrect or loose wiring
Power interruption (low voltage)
Corrective
Actions
Check wiring or tighten wiring connections if needed.
Verify the input voltage at the motor.
Replace the indoor unit PCB or motor.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...