SiUS342004EB
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
170
2.2 Accessing the BS Buttons on the PCB
It is not required to open the complete control box to access the BS buttons on the PCB and read
out the seven-segment display(s).
To access you can remove the service window cover (see figure). Now you can open the inspection
door of the control box cover (see figure). You can see the 3 BS buttons and the 3 seven-segment
displays and DIP switches.
Operate the switches and BS buttons with an insulated stick (such as a closed ballpoint pen) to
avoid touching of live parts.
Location of the segment displays, buttons and DIP switches:
Segment display indications:
1 Ser
v
ice window co
v
er
2 Inspection door
3 Main PCB with 3 se
v
en-segment displays
and 3 BS
bu
ttons
1
2
3
1
2
BS1BS2
DS1 DS2
BS3
X27A
1
3 seven-segment displays
2
BS
buttons
MODE (BS1)
for changing setting mode
SET (BS2), RETURN (BS3)
for changing field setting
DS1, DS2
DIP s
w
itches
Off
Blinking
On
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...