Troubleshooting by Error Code
SiUS342004EB
297
Part 6 Service Diagnosis
3.41 Wet Alarm
Applicable
Models
All outdoor unit models
Error Code
F4
Method of Error
Detection
In cooling operation, detect the condition under which liquid refrigerant returns to the compressor,
according to the temperature and pressure of each part.
Error Decision
Conditions
When the following wet state continues for a period of 90 minutes, an alert is issued.
An error is defined for 120 minutes.
Wet state in outdoor units
When the following wet state continues for a period of 45 minutes, an alert is issued.
Wet state in some of indoor units
Supposed
Causes
Defective suction pipe thermistor
Defective compressor suction thermistor
Defective discharge pipe thermistor
Defective high pressure sensor
Defective indoor unit electronic expansion valve
Dirty air filter
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...