background image

Guangzhou Hiseer Air Conditioning Co

Ltd

. ,

www.chinaheatpump.com

Split EVI Air to Water

Low Temp

Heat Pump

.

Summary of Contents for AW13

Page 1: ...Guangzhou Hiseer Air Conditioning Co Ltd www chinaheatpump com Split EVI Air to Water Low Temp Heat Pump ...

Page 2: ...water temperature varies according to ambient temperature Most components are well sealed to retain heat and prevent dripping L Features Triple functions Heating cooling and produce domestic hot water Outdoor unit Contains two fans blades and motors and aluminum finned copper coil heat exchanger Outdoor unit has not pre filled refrigerant Indoor unit Contains Hitachi EVI R410A compressor High effi...

Page 3: ... injection inlet and then injecting mixing and compressing process goes on at the same time until working room separates from injection inlet The gas state in working room change to state 2 from state 2 3 After working room separates from injection inlet the gas inside is compressed from state 2 to state 3 3 is normal heat pump Heat output increases almost in linear trend following the increase of...

Page 4: ...mption at 10 45 kW 9 4 4 8 Heat output Power consumption at 15 35 kW 8 6 3 9 Heat output Power consumption at 15 45 kW 8 5 4 8 Starting current A 55 Power 380 415V 3PH 50Hz Compressor HITACHI scroll Condenser Brazed plate heat exchanger Nominal flow heating medium l s 0 67 Internal pressure drop at nominal flow kPa 24 Air flow m 3 h 5000 Nominal output fan W 300 Max outgoing heating medium tempera...

Page 5: ...Performance curve Ambient temp Ambient temp 1 Flow temperature 35 Full load 2 Flow temperature 45 Full load Heating performance curve Ambient temp ...

Page 6: ...Dimension Outdoor unit Indoor unit ...

Page 7: ...Water pressure drop Optional internal water pump curve m3 h 10 20 30 1 0 2 0 3 0 4 0 40 KPa AW13 F 0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 Pressure mCE Flow m3 H Maximum speed Medium speed Mini speed ...

Page 8: ...Circulation pump Internal Option RT Inlet water temperature sensor Internal ELK Electric heater Internal Option ST Out water temperature sensor Internal VXV 3 way Valve Internal Option OT Outdoor temperature sensor Internal VVB Hot water tank External HT Hot water temperature sensor Internal FI Soft joint External ET suction gas temperature sensor Internal FS Automatic water supplement valve Exter...

Reviews: