DMS-R-IM
Installation
April 7, 2021
Digital Modular System - Rinse
3-12
NOTE
Recommended incoming power wire size and temperature
rating as below:
DMS-1218
:
Wire Size: 12AWG
Temperature Rating: 60°C
DMS-1826:
Wire Size: 8AWG
Temperature Rating: 60°C
Electrical installation
must be performed by a qualified electrician in accordance
with the electrical schematics provided with this manual.
No.
Description
1
A proper electrical drop must be supplied by the factory. Please refer
to the electrical schematics for power requirements.
Observe all precautions and installation procedures required for your
industry and location.
2
For each installation, first connect
phase to phase
, and then follow by
neutral to neutral
(if applicable), and lastly
ground to ground
.
3
Electrical power should be connected to a fused disconnect switch,
which is provided by the customer.
Line side
of the fused disconnect switch is connected to the
factory power.
Load side
of the fused disconnect is connected to the live side
of the master control relay (MCR) or main power terminals.
4
Please refer to
Generator Manual
for detailed information regarding
the generators and transducers supplied with this console.
5
If you are interfacing a Crest RIGIBOT materials handling unit to the
cleaning console, this is done simply by snapping together the
connectors.