Appendix
B-18
7SA6 Manual
C53000-G1176-C156-2
3510
Op.mode with AR
Synchronism and
Voltage Check
with consideration of CB
closing time
without consideration of CB
closing time
without consideration of CB
closing time
Operating mode with AR
3511
Max. Volt. Diff
Synchronism and
Voltage Check
1.0..40.0 V
2.0 V
Maximum voltage difference
3512
Max. Freq. Diff
Synchronism and
Voltage Check
0.03..2.00 Hz
0.10 Hz
Maximum frequency difference
3513
Max. Angle Diff
Synchronism and
Voltage Check
2..60
°
10
°
Maximum angle difference
3515A
SYNC-CHECK
Synchronism and
Voltage Check
YES
NO
YES
Live bus / live line and Sync before AR
3516
Usync> U-line<
Synchronism and
Voltage Check
YES
NO
NO
Live bus / dead line check before AR
3517
Usync< U-line>
Synchronism and
Voltage Check
YES
NO
NO
Dead bus / live line check before AR
3518
Usync< U-line<
Synchronism and
Voltage Check
YES
NO
NO
Dead bus / dead line check before AR
3519
OVERRIDE
Synchronism and
Voltage Check
YES
NO
NO
Override of any check before AR
3530
Op.mode with MC
Synchronism and
Voltage Check
with consideration of CB
closing time
without consideration of CB
closing time
without consideration of CB
closing time
Operating mode with Man.Cl
3531
MC maxVolt.Diff
Synchronism and
Voltage Check
1.0..40.0 V
2.0 V
Maximum voltage difference
3532
MC maxFreq.Diff
Synchronism and
Voltage Check
0.03..2.00 Hz
0.10 Hz
Maximum frequency difference
3533
MC maxAngleDiff
Synchronism and
Voltage Check
2..60
°
10
°
Maximum angle difference
3535A
MC SYNCHR
Synchronism and
Voltage Check
YES
NO
YES
Live bus / live line and Sync before MC
3536
MC Usyn> Uline<
Synchronism and
Voltage Check
YES
NO
NO
Live bus / dead line check before
Man.Cl
3537
MC Usyn< Uline>
Synchronism and
Voltage Check
YES
NO
NO
Dead bus / live line check before
Man.Cl
3538
MC Usyn< Uline<
Synchronism and
Voltage Check
YES
NO
NO
Dead bus / dead line check before
Man.Cl
3539
MC O/RIDE
Synchronism and
Voltage Check
YES
NO
NO
Override of any check before Man.Cl
3701
Uph-e>(>)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode Uph-e overvoltage
prot.
3702
Uph-e>
Voltage Protection
1.0..170.0 V;
∞
85.0 V
Uph-e> Pickup
3703
T Uph-e>
Voltage Protection
0.00..30.00 sec;
∞
2.00 sec
T Uph-e> Time Delay
3704
Uph-e>>
Voltage Protection
1.0..170.0 V;
∞
100.0 V
Uph-e>> Pickup
3705
T Uph-e>>
Voltage Protection
0.00..30.00 sec;
∞
1.00 sec
T Uph-e>> Time Delay
3709A
Uph-e>(>) RESET
Voltage Protection
0.50..0.98
0.98
Uph-e>(>) Reset ratio
3711
Uph-ph>(>)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode Uph-ph overvoltage
prot.
3712
Uph-ph>
Voltage Protection
2.0..220.0 V;
∞
150.0 V
Uph-ph> Pickup
3713
T Uph-ph>
Voltage Protection
0.00..30.00 sec;
∞
2.00 sec
T Uph-ph> Time Delay
3714
Uph-ph>>
Voltage Protection
2.0..220.0 V;
∞
175.0 V
Uph-ph>> Pickup
3715
T Uph-ph>>
Voltage Protection
0.00..30.00 sec;
∞
1.00 sec
T Uph-ph>> Time Delay
3719A
Uphph>(>) RESET
Voltage Protection
0.50..0.98
0.98
Uph-ph>(>) Reset ratio
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...