Functions
6-300
7SA6 Manual
C53000-G1176-C156-2
Trip Seal-in
(Reclosure
Lock-out)
When tripping the circuit-breaker with a protection function reclosure must often be
locked until the cause for the protection function operation is found. 7SA6 therefore
provides the integrated reclosure lock-out function.
The lock-out state (“
LOCKOUT
”) is realized by a RS flipflop which is protected against
auxiliary voltage failure (see Figure 6-153). The RS flipflop will be set via a binary input
“
>Lockout SET
” (FNo
385
). With the output alarm “
LOCKOUT
” (FNo
530
), if intercon-
nected correspondingly, a reclosure of the circuit-breaker (e.g. for automatic reclos-
ure, manual close signal, synchronization, closing via control) can be blocked. Only
once the cause for the protection operation is known, should the lock-out be reset by
a manual reset via binary input “
>Lockout RESET
” (FNo
386
).
Figure 6-153 Trip circuit seal-in (reclosure lock-out)
The conditions which cause reclosure lock-out and the control commands which have
to be locked can be set individually. The two inputs and the output can be wired via
the correspondingly allocated binary inputs and outputs or be linked via user-defined
logic functions (CFC).
If, for example, each trip by the protection function should be sealed, then combine the
tripping command “
Relay TRIP
” (FNo
511
) with the binary input “
>Lockout SET
”.
If automatic reclosure is applied, only the final trip of the protection function should es-
tablish closing lock-out. Then combine the output alarm “
Definitive TRIP
” (FNo
536
) with the lock-out input “
>Lockout SET
”, so that the lock-out function is not es-
tablished when an automatic reclosure is still expected to come.
In the most simple case the output alarm “
LOCKOUT
” (FNo 530) can be allocated to
the output which trips the circuit-breaker without creating further links. Then the trip-
ping command is sealed until the lock-out is reset via the binary reset input. Naturally
it has to be ensured in advance that the close coil at the circuit breaker — as is usually
done — is locked as long as a tripping command is maintained.
The output alarm “
LOCKOUT
” can also be applied to interlock certain closing com-
mands (externally or via CFC), e.g. by combining the output alarm with the binary input
“
>Close Cmd. Blk
” (FNo
357
) or by connecting the inverted alarm with the bay in-
terlocking of the feeder.
The reset input “
>Lockout RESET
” (FNo
386
) resets the interlocking state. This input
is initiated by an external device which is protected against unauthorized or uninten-
tional operation. The lock-out state can also be reset by internal sources, e.g. a func-
tion key, operation of the device or using DIGSI
®
4 on a PC.
For each case please make sure the corresponding logical combinations, security
measures, etc. are taken into account for the routing of the binary inputs and outputs
(Section 5.2) and are also considered for the setting of user-defined logic functions
(Section 5.3), if necessary.
Breaker Tripping
Alarm Suppression
While on feeder without automatic reclosure every trip command by a protection func-
tion is final, it is desirable, when using automatic reclosure, to prevent the operation
detector of the circuit-breaker (intermediate contact on the breaker) from sending an
alarm if the trip of the breaker is not final (Figure 6-154).
S
R
Q
>LOCKOUT Set
>LOCKOUT Reset
LOCKOUT
FNo
385
FNo
386
FNo
530
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...