Technical Data
10-4
7SA6 Manual
C53000-G1176-C156
- 7SA641
∗
–
∗
A/J/M/P
13(allocatable)
- 7SA641
∗
–
∗
B/K
20(allocatable)
- 7SA642
∗
–
∗
A/J/M/R
21(allocatable)
- 7SA642
∗
–
∗
B/K/N/S
29(allocatable)
- 7SA642
∗
–
∗
C/L
33(allocatable)
Nominal voltage
24 VDC to 250 VDC in 3 ranges, bipolar
Switching thresholds
adjustable with jumpers
– for nominal voltages 24/48 VDC
U
pick-up
≥
19 VDC
60/110/125 VDC
U
drop-off
≤
14 VDC
– for nominal voltages 110/125/
U
pick-up
≥
88 VDC
220/250 VDC
U
drop-off
≤
66 VDC
– for nominal voltages 220/250 VDC
U
pick-up
≥
176 VDC
U
drop-off
≤
117 VDC
Current consumption, energized
approx. 1.8 mA
independent of the control voltage
Maximum permissible voltage
300 VDC
Impulse filter on input
220 nF coupling capacity at 220 V
with recovery time >60 ms
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...