Functions
6-128
7SA6 Manual
C53000-G1176-C156-2
The instantaneous tripping following manual closure is blocked as long as the inrush-
stabilization recognizes a rush current. This prevents instantaneous tripping by a
stage which, under normal conditions, is sufficiently delayed during energization of a
transformer.
6.7.2
Applying the Function Parameter Settings
During the configuration of the device functions (refer to Section 5.1, address
131
Earth Fault O/C
) it was determined which characteristics of the overcurrent time
protection would be available. Depending on the configuration selected there, and the
ordered version of the relay, only those parameters applicable to the available curves
are accessible now.
By means of the parameter
3101
FCT EarthFltO/C
the earth fault protection can
be switched
On
or
Off
. This refers to all functions of the earth fault protection.
Each individual stage, if not required, can be set to
Inactive
(see below).
Blocking
The earth fault protection can be blocked by the distance protection to give preference
to the selective fault clearance by the distance protection over tripping by the earth
fault protection. In setting address
3102
BLOCK for Dist.
it is determined whether
blocking is done during each fault detection of the distance protection (
every Pick-
up
) or only during single-phase fault detection by the distance protection (
single-
phase Pickup
) or only during multiple-phase fault detection by the distance protec-
tion (
multi-phase Pickup
). If blocking is not required, the setting
No
is applied.
The earth fault protection should be blocked during single-pole automatic reclose
dead time, to avoid pick-up with the false zero sequence values arising during this
state (address
3103
BLOCK 1pDeadTim
). A setting of
Yes
is therefore only required
if single-pole tripping is possible. Otherwise the setting
No
(presetting) remains.
Definite Time
Stages
First of all, the mode for each stage is set:
Op. mode 3I0>>>
(address
3110
),
Op. mode 3I0>>
(address
3120
) and
Op. mode 3I0>
(address
3130
). Each stage
can be set to operate
Forward
(usually towards line) or
Reverse
direction (usually
towards busbar) or
Non-Directional
(in both directions). If a single stage is not re-
quired, set its mode to
Inactive
.
The definite time stages
3I0>>>
(address
3111
),
3I0>>
(address
3121
) and
3I0>
(address
3131
) can be used for a three-stage definite time overcurrent protection.
They can also be combined with the inverse time stage
3I0p PICKUP
(address
3141
,
see below). The pick up thresholds should in general be selected such that the most
sensitive stage picks up with the smallest expected earth fault current.
The 3I
0
>> und 3I
0
>>> stages are best suited for fast tripping stages (instantaneous),
as these stages use an abridged filter with shorter response time. On the other hand,
the stages 3I0> and 3I0p are best-suited for very sensitive earth fault detection due to
their effective method of suppressing harmonics.
If no inverse time stage but rather a fourth definite time stage is required, the “inverse
time” stage can be implemented as a definite time stage. This must already be taken
regard of during the configuration of the protection functions (refer to Section 5.1,
address
131
Earth Fault O/C
=
Definite Time
). For this stage, the address
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...