In the event of an earth fault the induced longitudinal voltage must neither exceed
60 % of the isolation voltage of the pilot wires nor 60 % of the isolation of the device.
The pilot wire comparison is therefore only suited for short lines.
6.6.1.9
Reverse Interlocking
If the Distance Protection 7SA6 is used as back-up protection in single-end fed trans-
former feeders, the reverse interlocking function ensures a fast protection of the bus-
bar without endangering the selectivity for faults on the outgoing feeders.
According to Figure 6-65 the distance zones Z1 and Z2 serve as back-up stages for
faults on the outgoing lines, for example a fault in F2. For distance grading the shortest
outgoing line is to be used.
The overreach zone Z1B, whose delay time T1B must be set longer than the pickup
time Ta of the protection devices of the outgoing lines, is blocked after the pickup of
an inferior protection. The pickup signal is sent (according to Figure 6-65) via the re-
ceive input of the Distance Protection.
If no signal is received this zone guarantees fast tripping of the busbar for
- faults on the busbar, such as for example in F1,
- failure of the line protection during a fault, such as for example in F2.
The reverse interlocking of the Distance Protection is performed by specific release or
blocking of the overreach zone Z1B. It can be realized by the blocking mode (see Fig-
ure 6-65) or the release mode.
To avoid transient false signals after clearance of external faults, the blocking condi-
tion of the reverse interlocking is extended by a transient blocking time (TB in Figure
6-65).
Figure 6-65
Reverse interlocking — functional principle and grading example
F1
F2
Z1
Z1B
T1
T1B
T2
Ta
Pickup
L+
Pick.
L+
Pick
.
L+
Pick
.
L+
Shortest Line
&
TB
0
Z1B
T1B
Direc
.
7SA6
Tripping
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...