Functions
6-66
7SA6 Manual
C53000-G1176-C156-2
1341
Op. mode Z5
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode Z5
1342
R(Z5) Ø-Ø
0.050..250.000 Ohm
12.000 Ohm
R(Z5), Resistance for ph-ph-
faults
1343
X(Z5)+
0.050..250.000 Ohm
12.000 Ohm
X(Z5)+, Reactance for Forward
direction
1344
RE(Z5) Ø-E
0.050..250.000 Ohm
12.000 Ohm
RE(Z5), Resistance for ph-e
faults
1345
T5 DELAY
0.00..30.00 sec;
∞
0.90 sec
T5 delay
1346
X(Z5)-
0.050..250.000 Ohm
4.000 Ohm
X(Z5)-, Reactance for Reverse
direction
Addr.
Setting Title
Setting Options
Default Setting
Comments