Installation and Commissioning
8-37
7SA6 Manual
C53000-G1176-C156-2
Interface RS232
The interface RS232 can be modified to interface RS485, according to Figure 8-21.
Figure 8-19 shows the printed circuit board C–CPU–2 and the interface modules. Fi-
gure 8-20 shows the location of the jumpers of interface RS232 on the interface mo-
dule.
Terminating resistors are not required. They are disconnected.
Figure 8-20 Location of the jumpers for configuration of RS232
With jumper X11, CTS is activated which is necessary for the communication with the
modem.
*) Default Setting
Jumper setting 2–3:
the connection to the modem is usually done with star coupler
or optical fibre converter. Therefore the modem control signal according to RS232
standard DIN 66020 is not available. Modem signals are not required since communi-
cation to SIPROTEC
®
devices is always carried out in the half duplex mode. Use
connetion cable with ordering number 7XV5100–4.
Jumper setting 1–2:
this setting makes the modem signal available, i. e. for a direct
RS232-connection between the SIPROTEC
®
device and the modem this setting can
Table 8-22
Exchangeable interface modules
Interface
Mounting Location
Exchange Module
System Interface
or Analog Output
B
only interface modules that can
be ordered as an option of the
device
(see
Appendix
).
AN20
Analog Output
D
AN20
Tabelle 8-23 Jumper setting of CTS (Clear-To-Send) on the interface module
Jumper
/CTS from interface RS232
/CTS triggered by /RTS
X11
1–2
2–3 *)
X3
1
3
2
X10
1
3
2
8X
1
3
2
X12
1
3
2
C53207-
A324-B180
1
3
2
X1
1
X6
X7
X4
X5
1
3
2
1
3
2
X1
3
Jumper
Terminating Resistors
disconnected
X3
1–2 *)
X4
1–2 *)
*) Default Setting
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...