Functions
6-286
7SA6 Manual
C53000-G1176-C156-2
6.21.1.6 Group Alarms
Certain messages of the monitoring functions are already combined to group alarms.
Table 6-14 shows an overview of these group alarms an their composition.
6.21.2 Applying the Function Parameter Settings
The sensitivity of the measured value monitoring can be changed. In the factory, pre-
settings based on experience have already been applied, which should be sufficient
for most applications. If particularly high operational asymmetries of the currents and/
or voltages are expected, or if one or more monitoring functions pick up sporadically
during normal operation, the sensitivity setting(s) should be reduced.
In address
2901
MEASURE. SUPERV
the measured value monitoring can be switched
ON
or
OFF
.
Table 6-14
Group alarms
Group alarms
Composed of
FNo
Designation
FNo
Meaning
161
Fail I Superv.
162
163
Fail
Σ
I
Fail I balance
164
Fail U Superv.
165
167
168
Fail
Σ
Uphe
Fail U balance
Fail U absent
160
Alarm Sum Event
162
163
165
167
168
169
170
361
171
177
193
3464
183
184
185
186
187
188
189
Fail
Σ
I
Fail I balance
Fail
Σ
Uphe
Fail U balance
Fail U absent
VT Fuse fail > 10 s
VT FuseFail
>Fail:Feeder VT
Fail Ph.Seq.
Fail battery
Alarm NO calibr
Topol complete, negated
Error Board 1
Error Board 2
1
)
Error Board 3
1
)
Error Board 4
1
)
Error Board 5
1
)
Error Board 6
1
)
Error Board 7
1
)
140
Error Sum Alarm
144
168
192
194
181
Error 5V
Fail U absent
Error 1A/5A wrong
Error neutral
Error A/D-conv.
1
) depending on the version (number of printed circuit boards)
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...