Functions
6-269
7SA6 Manual
C53000-G1176-C156-2
6.20
Analog Outputs (optional)
6.20.1 Method of Operation
Depending on the ordering version the 7SA6 relay up to four analog outputs are avail-
able. During the configuration of the functional scope (see Figure 5.1) it was deter-
mined which values may be transmitted via these interfaces. Up to four outputs can
be selected out of the following list:
•
Measured value I
L2
(current of phase L2) in per cent of the operational nominal
current
•
Measured value U
L2–L3
(phase-to-phase voltage L2-L3) in per cent of the opera-
tional nominal voltage
•
Measured value |P| (value of active power) in per cent of the operational nominal
power
√
3·U
N
·I
N
•
Measured value |Q| (value of reactive power) in per cent of the operational nominal
apparent power
√
3·U
N
·I
N
•
Fault distance d in per cent of line length on the basis of the configured reactance
per unit length and the line length (Address
1110
to
1113
, see also Subsection
6.1.3)
•
Fault distance d in kilometres or miles, depending on the configured length unit (Ad-
dress
236
, see also Subsection 6.1.1), on the basis of the configured reactance per
unit length (Address
1110
or
1112
, see also Subsection 6.1.3)
•
Fault current I
max
, i. e. the maximum of 3 phase currents during clearance of the
last fault, primary in Ampere, on the basis of the configured primary and secondary
nominal current (Address
205
and
206
, see also Subsection 6.1.1)
The operational nominal values are the nominal values configured according to Ad-
dress
1103
and
1104
(see also Subsection 6.1.3).
The analog values are output as current source. The nominal range of the analog out-
puts is 0 mA to 20 mA, the operating range may reach up to 22.5 mA. The conversion
factor and the valid range can be set.
6.20.2 Applying the Function Parameter Settings
Measure Values
Once the measured values are selected (Section 5.1, Addresses
150
to
153
), set the
conversion factor and the valid range for the available outputs, as follows:
for analog output 1 at mounting location “B” (Port B1):
Address
5001
20 mA (B1) =
value in % to be indicated at 20 mA
Address
5006
MIN VALUE (B1)
the minimum value permitted
for analog output 2 at mounting location “B” (Port B2):
Address
5011
20 mA (B2) =
value in % to be indicated at 20 mA
Address
5016
MIN VALUE (B2)
the minimum value permitted
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...