Control During Operation
7-37
7SA6 Manual
C53000-G1176-C156-2
From the
DeviceFront
With a device ready for operation, first press the
key. The
MAIN MENU
appears.
Using the
key, highlight the menu item
Test/Diagnose
, and then press the
key to enter sub-menu.
TEST/DIAGNOSE
will appear at the top of the menu.
At this point, highlight the menu item
Test Enable
using the
key, and then press
the
key to enter sub-menu.
TEST ENABLE
will appear at the top of the menu. See
Figure 7-37.
Figure 7-37
Applying Test Mode from the Operator Control Panel
To start
Test mode
, press the
key, enter the password N° 4 (for test and diag-
nostics) and confirm with the
key. A new window appears with the options
ON
and
OFF
. Use the
and
keys to select the desired mode, and press the
key. The
question “
Are you sure?
” is displayed. Highlight the desired response and press
the
key. If the mode is changed, the footer shows the message “
Control Ex-
ecuted
” for a short time.
Use the
key to return to the
TEST/DIAGNOSE
level; press the
key to return to
the
MAIN MENU
.
The procedure for changing the Block Data Transmission mode is the same. See Fig-
ure 7-38 (simplified).
Figure 7-38
Applying a Block of Data Transmission from the Front Panel (simplified)
The settings for the test mode and the data transmission block are normally
OFF
. Def-
initions:
−
Test mode
– With the
ON
setting, the “test mode”-bit is transferred for messages
compatible with IEC 60 870–5–103.
−
DataStop
– With the
ON
setting, no messages or measured values are trans-
ferred (“transfer block”).
From PC with
DIGSI
®
4
Click on
Device
in the menu bar to reach the commands
Block Data Transmis-
sion
and
Test Mode
. See Figure 7-39.
MENU
TEST ENABLE
--------------------
>
Test mode OFF
TEST DIAGNOSE 02/06
--------------------
Device Reset –> 1
>
Test Enable –> 2
Blk Data Trans–> 3
Hardware Test –> 4
Set/Reset –> 11
SIEMENS Intern 12
ENTER
ENTER
ENTER
ENTER
MENU
TEST/DIAGNOSE 03/06
--------------------
>
Blk Data Trans–> 3
Hardware Test –> 4
BLK DATA TRANS
--------------------
>
DataStop OFF
:
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...