Technical Data
10-20
7SA6 Manual
C53000-G1176-C156
Tolerances
current
3 % of set value or 1% of nominal current
time
1 % of set value or 10 ms
The set times are pure delay times.
1) Secondary values based on I
N
= 1 A; for I
N
= 5 A the current values must be multiplied by 5.
Overcurrent stage
(definite time)
Pickup value
3I
0
>
0.05 A to 25.00 A
1
)
(steps 0.01 A)
or
0.003 A to 25.000 A
1
) (steps 0.001 A)
Delay time
T
3I0>
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Drop-off to pick-up ratio
approx. 0.95 for I/I
N
≥
0.5
Pickup time (for 1.5* Setting Value)
approx. 45 ms
(for
≥
2 * Setting Value)
approx. 35 ms
Drop-off time
approx. 30 ms
Tolerances
current
3 % of set value or 1% of nominal current
time
1 % of set value or 10 ms
The set times are pure delay times.
1) Secondary values based on I
N
= 1 A; for I
N
= 5 A the current values must be multiplied by 5.
Overcurrent stage
(inverse time acc.
IEC)
Pickup value
3I
0P
0.05 A to 25.00 A
1
)
(steps 0.01 A)
or
0.003 A to 25.000 A
1
) (steps 0.001 A)
Time factor
T
3I0P
0.05 s to 3.00 s
(steps 0.01 s)
or
∞
(ineffective)
Additional time delay
T
3I0Pverz
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Characteristics
see Figure 10-1
Tolerances
current
pickup at 1.05
≤
I/3I
0P
≤
1.15
times
5 % ± 15 ms for 2
≤
I/3I
0P
≤
20
and T
3I0P
/s
≥
1
1) Secondary values based on I
N
= 1 A; for I
N
= 5 A the current values must be multiplied by 5.
Overcurrent stage
(inverse time acc.
ANSI)
Pickup value
3I
0P
0.05 A to 25.00 A
1
)
(steps 0.01 A)
or
0.003 A to 25.000 A
1
) (steps 0.001 A)
Time factor
D
3I0P
0.50 s to 15.00 s
(steps 0.01 s)
or
∞
(ineffective)
Additional time delay
T
3I0Pverz
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Characteristics
see Figures 10-2 and 10-3
Tolerances
current
pickup at 1.05
≤
I/3I
0P
≤
1.15
times
5 % ± 15 ms for 2
≤
I/3I
0P
≤
20
and D
3I0P
/s
≥
1
1) Secondary values based on I
N
= 1 A; for I
N
= 5 A the current values must be multiplied by 5.
Overcurrent stage
(logarithmic in-
verse)
Pickup value
3I
0P
0.05 A to 25.00 A
1
)
(steps 0.01 A)
or
0.003 A to 25.000 A
1
) (steps 0.001 A)
Startstromfaktor
3
I0P FAKTOR
1.0 to 4.0
(steps 0.1)
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...