Control During Operation
7-16
7SA6 Manual
C53000-G1176-C156-2
If the device is provided with earth fault detection in a non-earthed system, also the
components of the earth fault current (active and reactive components) are indicated.
In addition to those measured values listed in the table, it is possible to retrieve user
defined measurement, metering and set points, if these were generated during the
configuration of the device according to Section 5.2 and/or 5.3 “Generating user de-
finable functions with CFC”.
Table 7-1
Operational measured values
Measured values
primary
secondary
% referred to
I
L1
, I
L2
, I
L3
phase currents
A
A
rated operational current
1
)
3I
0
earth currents
A
A
rated operational current
1
)
I
1
, I
2
pos. and neg. seq. currents
A
A
rated operational current
1
)
3I0
sen
sensitive earth current
A
mA
rated operational current
1
)
3
)
I
Y
, I
P
transformer star point current or
earth current in the parallel line
A
A
rated operational current
1
)
3
)
U
L1–L2
, U
L2–L3
, U
L3–L1
line voltages
kV
V
rated operational voltage
2
)
U
L1–E
, U
L2–E
, U
L3–E
phase-earth voltages
kV
V
rated operational voltage
/
√
3
2
)
3U
0
displacement voltage
kV
V
rated operational voltage
·
√
3
2
)
4
)
U
X
voltage at the measuring input U
4
kV
V
rated operational voltage
/
√
3
2
)
U
1
, U
2
pos. and neg. seq. voltages
kV
V
rated operational voltage
/
√
3
2
)
R
L1–E
, R
L2–E
, R
L3–E
R
L1–L2
, R
L1–L2
, R
L3–L1
operational resistance of all phase
loops
Ω
Ω
—
X
L1–E
, X
L2–E
, X
L3–E
X
L1–L2
, X
L2–L3
, X
L3–L1
operational reactance of all phase
loops
Ω
Ω
—
S, P, Q
apparent, real, and reactive power MVA, MW,
MVAR
—
√
3·U
N
·I
N
rated operational values
1
)
2
)
cos
ϕ
power factor
(abs)
(abs)
—
f
frequency
Hz
Hz
rated frequency
Θ
L1
/
Θ
trip
,
Θ
L2
/
Θ
trip
,
Θ
L3
/
Θ
trip
thermal value of each phase
related to trip value
—
—
temperature rise
Θ
/
Θ
trip
thermal value,
related to trip value, calculated
according to the configured method
—
—
temperature rise
U
line
, U
sync
, U
diff
line voltage, busbar voltage and
voltage magnitude difference
(for synchronism check)
kV
—
—
f
line
, f
sync
, f
diff
line voltage, busbar voltage and
frequency difference
(for synchronism check)
Hz
—
—
ϕ
diff
magnitude of the phase angle dif-
ference between line and busbar
(for sychronism check)
°
—
—
3I0senA, 3I0senR
active and reactive components of
earth fault current
A
mA
—
1
) acc. to address
1104
(refer to Sub-section 6.1.3)
2
) acc. to address
1103
(refer to Sub-section 6.1.3)
3
) with consideration of the factor
221
I4/Iph CT
(refer to Sub-section 6.1.1)
4
) with consideration of the factor
211
Uph / Udelta
(refer to Sub-section 6.1.1)
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...