Appendix
B-21
7SA6 Manual
C53000-G1176-C156-2
4505A
PROT 1 T-DELAY
Protection Interface
(Port D+E)
0.1..30.0 ms
30.0 ms
Prot 1: Maximal permissible delay time
4509
T-DATA DISTURB
Protection Interface
(Port D+E)
0.05..2.00 sec
0.10 sec
Time delay for data disturbance alarm
4510
T-DATAFAIL
Protection Interface
(Port D+E)
0.0..60.0 sec
6.0 sec
Time del for transmission failure alarm
4511
Td ResetRemote
Protection Interface
(Port D+E)
0.00..300.00 sec;
∞
0.00 sec
Remote signal RESET DELAY for
comm.fail
4701
ID OF RELAY 1
Protection Interface
(Port D+E)
1..65534
1
Identification number of relay 1
4702
ID OF RELAY 2
Protection Interface
(Port D+E)
1..65534
2
Identification number of relay 2
4703
ID OF RELAY 3
Protection Interface
(Port D+E)
1..65534
3
Identification number of relay 3
4710
LOCAL RELAY
Protection Interface
(Port D+E)
relay 1
relay 2
relay 3
relay 1
Local relay is
5001
20 mA (B1) =
AnalogOutputs
10.0..1000.0 %
200.0 %
20 mA (B1) correspond to
5002
20 mA (B1) =
AnalogOutputs
10..100000 A
20000 A
20 mA (B1) correspond to
5003
20 mA (B1) =
AnalogOutputs
1.0..1000.0 km
50.0 km
20 mA (B1) correspond to
5004
20 mA (B1) =
AnalogOutputs
1.0..1000.0 Miles
50.0 Miles
20 mA (B1) correspond to
5006
MIN VALUE (B1)
AnalogOutputs
0.0..5.0 mA
4.0 mA
Output value (B1) valid from
5007
NEG VALUE (B1)
AnalogOutputs
1.00..22.50 mA
19.84 mA
Output value (B1) for negative values
5008
OVERFLOW (B1)
AnalogOutputs
1.00..22.50 mA
22.50 mA
Output value (B1) for overflow
5009
Tmax OUTPUT(B1) AnalogOutputs
0.10..180.00 sec;
∞
5.00 sec
Maximum output time (B1)
5011
20 mA (B2) =
AnalogOutputs
10.0..1000.0 %
200.0 %
20 mA (B2) correspond to
5012
20 mA (B2) =
AnalogOutputs
10..100000 A
20000 A
20 mA (B2) correspond to
5013
20 mA (B2) =
AnalogOutputs
1.0..1000.0 km
50.0 km
20 mA (B2) correspond to
5014
20 mA (B2) =
AnalogOutputs
1.0..1000.0 Miles
50.0 Miles
20 mA (B2) correspond to
5016
MIN VALUE (B2)
AnalogOutputs
0.0..5.0 mA
4.0 mA
Output value (B2) valid from
5017
NEG VALUE (B2)
AnalogOutputs
1.00..22.50 mA
19.84 mA
Output value (B2) for negative values
5018
OVERFLOW (B2)
AnalogOutputs
1.00..22.50 mA
22.50 mA
Output value (B2) for overflow
5019
Tmax OUTPUT(B2) AnalogOutputs
0.10..180.00 sec;
∞
5.00 sec
Maximum output time (B2)
5021
20 mA (D1) =
AnalogOutputs
10.0..1000.0 %
200.0 %
20 mA (D1) correspond to
5022
20 mA (D1) =
AnalogOutputs
10..100000 A
20000 A
20 mA (D1) correspond to
5023
20 mA (D1) =
AnalogOutputs
1.0..1000.0 km
50.0 km
20 mA (D1) correspond to
5024
20 mA (D1) =
AnalogOutputs
1.0..1000.0 Miles
50.0 Miles
20 mA (D1) correspond to
5026
MIN VALUE (D1)
AnalogOutputs
0.0..5.0 mA
4.0 mA
Output value (D1) valid from
5027
NEG VALUE (D1)
AnalogOutputs
1.00..22.50 mA
19.84 mA
Output value (D1) for negative values
5028
OVERFLOW (D1)
AnalogOutputs
1.00..22.50 mA
22.50 mA
Output value (D1) for overflow
5029
Tmax OUTPUT(D1) AnalogOutputs
0.10..180.00 sec;
∞
5.00 sec
Maximum output time (D1)
5031
20 mA (D2) =
AnalogOutputs
10.0..1000.0 %
200.0 %
20 mA (D2) correspond to
5032
20 mA (D2) =
AnalogOutputs
10..100000 A
20000 A
20 mA (D2) correspond to
5033
20 mA (D2) =
AnalogOutputs
1.0..1000.0 km
50.0 km
20 mA (D2) correspond to
5034
20 mA (D2) =
AnalogOutputs
1.0..1000.0 Miles
50.0 Miles
20 mA (D2) correspond to
5036
MIN VALUE (D2)
AnalogOutputs
0.0..5.0 mA
4.0 mA
Output value (D2) valid from
5037
NEG VALUE (D2)
AnalogOutputs
1.00..22.50 mA
19.84 mA
Output value (D2) for negative values
5038
OVERFLOW (D2)
AnalogOutputs
1.00..22.50 mA
22.50 mA
Output value (D2) for overflow
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...