Functions
6-215
7SA6 Manual
C53000-G1176-C156-2
“
AR Sync.Request
” (F.No.
2865
)
Request for sync check measurement to an external device. This information appears
at the end of a dead time after a three-pole trip if a synchro–check request was set for
the corresponding cycle. Reclosure only takes place when the synchro–check device
has granted release “
>Sync.release
” (F.No.
2731
).
“
>Sync.release
” (F.No.
2731
)
Release of reclosure by an external synchro–check device if this was requested by the
output information “
AR Sync.Request
” (F.No.
2865
).
.
F.No.
Alarm
Comments
2701
>AR on
>AR: Switch on auto-reclose function
2702
>AR off
>AR: Switch off auto-reclose function
2703
>AR block
>AR: Block auto-reclose function
2711
>AR Start
>External start of internal Auto reclose
2712
>Trip L1 AR
>AR: External trip L1 for AR start
2713
>Trip L2 AR
>AR: External trip L2 for AR start
2714
>Trip L3 AR
>AR: External trip L3 for AR start
2715
>Trip 1pole AR
>AR: External 1pole trip for AR start
2716
>Trip 3pole AR
>AR: External 3pole trip for AR start
2727
>AR RemoteClose
>AR: Remote Close signal
2731
>Sync.release
>AR: Sync. release from ext. sync.-check
2737
>BLOCK 1pole AR
>AR: Block 1pole AR-cycle
2738
>BLOCK 3pole AR
>AR: Block 3pole AR-cycle
2739
>BLK 1phase AR
>AR: Block 1phase-fault AR-cycle
2740
>BLK 2phase AR
>AR: Block 2phase-fault AR-cycle
2741
>BLK 3phase AR
>AR: Block 3phase-fault AR-cycle
2742
>BLK 1.AR-cycle
>AR: Block 1st AR-cycle
2743
>BLK 2.AR-cycle
>AR: Block 2nd AR-cycle
2744
>BLK 3.AR-cycle
>AR: Block 3rd AR-cycle
2745
>BLK 4.-n. AR
>AR: Block 4th and higher AR-cycles
2746
>Trip for AR
>AR: External Trip for AR start
2747
>Pickup L1 AR
>AR: External pickup L1 for AR start
2748
>Pickup L2 AR
>AR: External pickup L2 for AR start
2749
>Pickup L3 AR
>AR: External pickup L3 for AR start
2750
>Pickup 1ph AR
>AR: External pickup 1phase for AR start
2751
>Pickup 2ph AR
>AR: External pickup 2phase for AR start
2752
>Pickup 3ph AR
>AR: External pickup 3phase for AR start
2781
AR off
AR: Auto-reclose is switched off
2782
AR on
AR: Auto-reclose is switched on
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...