Appendix
B-12
7SA6 Manual
C53000-G1176-C156-2
2910
FUSE FAIL MON.
Measurement
Supervision
ON
OFF
ON
Fuse Failure Monitor
2911A
FFM U>(min)
Measurement
Supervision
10..100 V
30 V
Minimum Voltage Threshold U>
2912A
FFM I< (max)
Measurement
Supervision
0.10..1.00 A
0.10 A
Maximum Current Threshold I<
2913A
FFM U<max (3ph)
Measurement
Supervision
2..100 V
5 V
Maximum Voltage Threshold U<
(3phase)
2914A
FFM Idelta (3p)
Measurement
Supervision
0.05..1.00 A
0.10 A
Delta Current Threshold (3phase)
2915
V-Supervision
Measurement
Supervision
with current supervision
with current superv. and
CBaux
OFF
with current supervision
Voltage Failure Supervision
2916A
T V-Supervision
Measurement
Supervision
0.00..30.00 sec
3.00 sec
Delay Voltage Failure Supervision
2921
T mcb
Measurement
Supervision
0..30 ms
0 ms
VT mcb operating time
3001
Sens. Earth Flt
Sensitive Earth
Flt.(comp/ isol.
starp.)
Alarm Only
ON
OFF
Alarm Only
Sensitive Earth Flt.(comp/ isol. starp.)
3002
3U0>
Sensitive Earth
Flt.(comp/ isol.
starp.)
1..150 V
50 V
3U0> pickup
3003
Uph-e min
Sensitive Earth
Flt.(comp/ isol.
starp.)
10..100 V
40 V
Uph-e min of faulted phase
3004
Uph-e max
Sensitive Earth
Flt.(comp/ isol.
starp.)
10..100 V
75 V
Uph-e max of healthy phases
3005
3I0>
Sensitive Earth
Flt.(comp/ isol.
starp.)
0.003..1.000 A
0.050 A
3I0> Release directional element
3006
T Sens.E/F
Sensitive Earth
Flt.(comp/ isol.
starp.)
0.00..320.00 sec
1.00 sec
Time delay for sens. E/F detection
3007
T 3U0>
Sensitive Earth
Flt.(comp/ isol.
starp.)
0.00..320.00 sec
0.00 sec
Time delay for sens. E/F trip
3008A
TRIP Direction
Sensitive Earth
Flt.(comp/ isol.
starp.)
Forward
Reverse
Non-Directional
Forward
Direction for sens. E/F trip
3010
CT Err. I1
Sensitive Earth
Flt.(comp/ isol.
starp.)
0.003..1.600 A
0.050 A
Current I1 for CT Angle Error
3011
CT Err. F1
Sensitive Earth
Flt.(comp/ isol.
starp.)
0.0..5.0
°
0.0
°
CT Angle Error at I1
3012
CT Err. I2
Sensitive Earth
Flt.(comp/ isol.
starp.)
0.003..1.600 A
1.000 A
Current I2 for CT Angle Error
3013
CT Err. F2
Sensitive Earth
Flt.(comp/ isol.
starp.)
0.0..5.0
°
0.0
°
CT Angle Error at I2
3101
FCT EarthFltO/C
Earth fault overcur-
rent
ON
OFF
ON
Earth Fault overcurrent function is
3102
BLOCK for Dist.
Earth fault overcur-
rent
with every Pickup
with single-phase Pickup
with multi-phase Pickup
NO
with every Pickup
Block E/F for Distance protection
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...