Functions
6-157
7SA6 Manual
C53000-G1176-C156-2
Figure 6-89
Logic diagram of the weak infeed tripping
*)
*)
>Dis.T.RecCh1L1
4207
U
L1
Two terminals
Three terminals
3202
Line Config.
&
„1“
Two terminals
Three terminals
2102
Line Config.
„1“
≥
1
EF OFF/BLOCK
50
40
ms
&
S
R
Q
I
E
3I
0
3105
3IoMin Teleprot
EF Pickup
≥
1
&
2501
FCT Weak Infeed
ECHO only
OFF
ECHO and TRIP
„1“
U
L1
2505
UNDERVOLT.
VT loss
&
Dist. OFF/BLOCK
40
ms
&
S
R
Q
&
PICKUP L1
CB closed L1
&
≥
1
&
W/I Pickup L1
>BLOCK Weak Inf
&
U
L2
U
L2
2505
UNDERVOLT.
&
S
R
Q
&
PICKUP L2
CB closed L2
&
≥
1
&
U
L3
U
L3
2505
UNDERVOLT.
&
S
R
Q
&
PICKUP L3
CB closed L3
&
≥
1
&
with earth fault protection
with dist. protection
*)
*)
*)
*)
applies to PUTT and
POTT;
with unblock schemes,
the ”unblock” signals
apply acc. to Fig. 6-61
*)
*)
*)
applies to direc. comp;
with unblock schemes the
“unblock” signals apply
4203
>Dis.T.RecCh1L2
4208
>Dis.T.RecCh1L3
4209
>Dis.Tel Rec.Ch1
4206
>Dis.Tel Rec.Ch2
4210
>EF Rec.Ch1
1318
>EF Rec.Ch2
1319
4232
W/I Pickup L2
4233
W/I Pickup L3
4234
Undervoltage
2502 Trip/Echo DELAY
2503
Trip EXTENSION
2502
2502
Trip/Echo DELAY
50
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...