Technical Data
10-27
7SA6 Manual
C53000-G1176-C156
10.6
Earth Fault Protection Teleprotection Schemes (optional)
Mode
For two line ends
with one channel for each direction
with three channels for each direction
For three line ends
with one channel for each direction and
oposite line end
Comparison
Schemes
Schemes
directional comparison pickup scheme
directional unblocking scheme
directional blocking scheme
Application
2-terminal lines
3-terminal lines
multi-terminal lines via CFC
Send signal prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Release signal prolongation
0.000 s to 30.000 s
(steps 0.001 s)
Transient blocking time
0.00 s to 30.00 s
(steps 0.01 s)
Waiting time for transient blocking
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Echo delay time
0.00 s to 30.00 s
(steps 0.01 s)
Echo impulse duration
0.00 s to30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
The set times are pure delay times
.
Overreach
schemes via
protection data
interface
(optional)
Methods
Directional comparison pickup scheme
Send signal prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Release signal prolongation
0.000 s to 30.000 s
(steps 0.001 s)
Transient blocking time
0.00 s to 30.00 s
(steps 0.01 s)
Waiting time for transient blocking
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Echo delay time
0.00 s to 30.00 s
(steps 0.01 s)
Echo pulse duration
0.00 s to30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
The set times are pure delay times
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...