Functions
6-17
7SA6 Manual
C53000-G1176-C156-2
6.1.3
General Protection Data
General protection data (
P.System Data 2
) includes settings associated with all
functions rather than a specific protective or monitoring function. In contrast to the
Power System Data 1 (
P.System Data 1
) as discussed in Sub-section 6.1.1, these
settings can be changed over with the setting groups. To modify these settings, select
the
SETTINGS
menu option
Group A
(setting group A), and then
Power System
Data 2 (P.System Data 2)
.
The other setting groups are
Group B
,
Group C
, and
Group D
, as described in
Subsection 6.1.2.
Rating of the
Protected System
The rated primary voltage (line voltage) and rated primary current (phase) of the pro-
tected system are entered in the address
1103
FullScaleVolt.
and
1104
FullScaleCurr.
. These parameters influence the display of the operational meas-
ured values in percent. If these ratings correspond to those of the voltage and current
transformers, the settings are the same as those in address
203
and
205
(Section
6.1.1).
General Line Data
The settings of the line data in this case refers to the common data which is independ-
ent on the actual distance protection grading.
The line angle (Address
1105
Line Angle
) may be derived from the line parameters.
The following applies:
where R
L
being the resistance and X
L
the reactance of the protected line. The line pa-
rameters may either apply to the entire line length, or be per unit of line length as the
quotient is independent of length. Furthermore it makes no difference if the quotients
were calculated with primary or secondary values.
The line angle plays an important role e.g. for the form of the polygons in the Distance
Protection or in the earth impedance matching with magnitude and angle.
Calculation example:
110 kV overhead line 150 mm
2
with the following data
R'
1
= 0.19
Ω
/km
X'
1
= 0.42
Ω
/km
The line angle is computed as follows
In address 1105 the setting
Line Angle
=
66
° is entered.
The per unit length reactance X' is entered as relative quantity
x'
, in address
1110
in
Ω
/km, when for example the unit of length is given in
km
(Address
236
, refer to Section
6.1.1 under “
Units of Length
” or under address
1112
in
Ω
/mile, when the unit of
length is given in
Miles
. The corresponding line length is entered in address
1111
Line Length
in kilometres or under address
1113
Line Length
in miles. If the unit
of length in address 236 is changed after the per unit length impedances in address
ϕ
tan
X
L
R
L
-------
=
ϕ
arc
X
L
R
L
-------
è
ø
æ
ö
tan
=
or
tan
ϕ
X
L
R
L
-------
X'
1
R'
1
--------
0.42
Ω
/km
0.19
Ω
/km
-----------------------------
2.21
=
=
=
=
ϕ
65.7°
=
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...