Functions
6-33
7SA6 Manual
C53000-G1176-C156-2
eter
1ph FAULTS
(address
1630A
) according to Table 6-2. In the non-earthed net-
work, the phase–to–phase loop is always selected for single–phase pick-up without
earth-fault detection.
The phases that have picked-up are signalled. If an earth fault has been detected, it
is also indicated. Pick-up will drop off if the signal falls below 95 % of the pick-up value.
6.2.2.2
Voltage-Dependent Current Fault Detection U/I
Mode of Operation
and Characteristic
The U/I pick-up is a per phase and per loop pick-up mode. Here the phase currents
must exceed a threshold , while the threshold value depends on the magnitude of the
loop voltage.
Pick-up due to earth faults in systems with a non-earthed system star point is effec-
tively suppressed by means of the measures described in Section 6.2.1.
The basic characteristics of the U/I pick-up can be seen from the current–voltage char-
acteristic shown in Figure 6-19. The first requirement for every phase pick-up is that
of the minimum current
Iph>
is exceeded. For the evaluation of phase–phase loops
both relevant phase currents have to exceed this value. Above this current the current
pick-up is voltage-dependent with the slope being determined by the settings U(I>)
and U(I>>). For short-circuits with large currents the overcurrent pick-up
Iph>>
(Sec-
tion 6.2.2.1) is superimposed. The bold dots in Figure 6-19 designate the settings
which determine the geometry of the current/voltage characteristic.
Loop pick-up will drop off if the signal falls below 95 % of the relevant current value or
exceeds 105 % of the relevant voltage value.
Table 6-2
Loop and phase indication for single–phase overcurrent pick-up
Pick-up
module
Earth-fault de-
tection
Parameter
1Ph FAULTS.
Valid
loop
Signalled
phase(s)
L1
L2
L3
no
no
no
phase–phase
L3–L1
L1–L2
L2–L3
L1, L3
L1, L2
L2, L3
L1
L2
L3
no
no
no
phase–earth
1
)
L1–E
L2–E
L3–E
L1
L2
L3
L1
L2
L3
yes
yes
yes
any
L1–E
L2–E
L3–E
L1, E
L2, E
L3, E
1
) Only possible in earthed networks
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...