Control During Operation
7-49
7SA6 Manual
C53000-G1176-C156-2
To perform control, confirm with the
key. A safety inquiry appears, “
Are you
sure?
”. If the response is “
YES
”, the switching operation is initiated (provided the Lo-
cal command is allowed). A message is displayed and recorded indicating the results
of the control action. Acknowledge this by pressing the
key once again.
The command is not executed if the switching operation is restricted. The operation
may be restricted for reasons pertaining to, for example, switching authority (see Sub-
section 7.4.6) or interlocking (see Sub-section 7.4.7). A message is displayed and re-
corded indicating the results of the control action. Acknowledge the message by
pressing the
key. Parameters to set control properties can be examined in the
display. Refer to Sub-section 7.4.4.
The
key can be used to return to
BREAKER/SWITCH
. Press the
key to return
to the
MAIN MENU
.
From PC with
DIGSI
®
4
When the
Online
window in DIGSI
®
4 is opened with a double click, the operating
functions for the device appear in the left part of the window. Clicking on
Control
dis-
plays the associated function selection in the data window. See Figure 7-50.
Figure 7-50
Window for Control of Operating Resources in DIGSI
®
4 - (example)
By double clicking on
Breaker/Switches
, a dialog field is opened in which the
present status of each switch is visible. See Figure 7-51. Control can be performed
from this dialog box provided the switching authority is set to
REMOTE
.
The switching authority is first transferred to DIGSI
®
4 at the moment the control win-
dow shown in Figure 7-51 is opened. The configuration matrix discussed in Section
5.2 determines the control devices that have information displayed in this field.
ENTER
ENTER
ENTER
MENU
:
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...