Technical Data
10-28
7SA6 Manual
C53000-G1176-C156
10.7
Weak-Infeed Tripping
Operation method
Phase segregated undervoltage detection after reception of a carrier signal from the
remote end
Undervoltage
Detection
Setting value
U
PhE
<
2 V to 70 V
(steps 1 V)
Drop-off to pick-up ratio
approx. 1.05
Pick-up tolerances
≤
5 % of set value or 0.5 V
Times
Release delay
0.00 s to 30.00 s
(steps 0.01 s)
Release prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...