Functions
6-213
7SA6 Manual
C53000-G1176-C156-2
3465
2.AR Tdead 2Flt
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3466
2.AR Tdead 3Flt
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3467
2.AR Tdead1Trip
0.01..1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3468
2.AR Tdead3Trip
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3469
2.AR: Tdead EV.
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3470
2.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before
reclosing
3471
2.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
3472
3.AR: START
YES
NO
NO
AR start allowed in this cycle
3473
3.AR: T-ACTION
0.01..300.00 sec;
∞
0.20 sec
Action time
3475
3.AR Tdead 1Flt
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3476
3.AR Tdead 2Flt
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3477
3.AR Tdead 3Flt
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3478
3.AR Tdead1Trip
0.01..1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3479
3.AR Tdead3Trip
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3480
3.AR: Tdead EV.
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3481
3.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before
reclosing
3482
3.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
3483
4.AR: START
YES
NO
NO
AR start allowed in this cycle
3484
4.AR: T-ACTION
0.01..300.00 sec;
∞
0.20 sec
Action time
3486
4.AR Tdead 1Flt
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3487
4.AR Tdead 2Flt
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3488
4.AR Tdead 3Flt
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3489
4.AR Tdead1Trip
0.01..1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3490
4.AR Tdead3Trip
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3491
4.AR: Tdead EV.
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3492
4.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before
reclosing
3493
4.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
3431
DLC or RDT
Without
Reduced Dead Time (RDT)
Dead Line Check (DLC)
Without
Dead Line Check or Reduced
Dead Time
3420
AR w/ DIST.
YES
NO
YES
AR with distance protection
Addr.
Setting Title
Setting Options
Default Setting
Comments
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...