Functions
6-158
7SA6 Manual
C53000-G1176-C156-2
To avoid a faulty pick up of the weak infeed function following tripping of the line and
reset of the fault detection, the function cannot pick up any more once a fault detection
in the affected phase was present (RS flip-flop in Figure 6-89).
In the case of the earth fault protection, the release signal is routed via the phase seg-
regated logic modules. Single-phase tripping is therefore also possible if, besides the
distance protection, the earth fault protection also issues a release condition.
6.9.2
Applying the Function Parameter Settings
It is a prerequisite for the operation of the weak infeed function that it was enabled dur-
ing the configuration of the device (Section 5.1) under address
125
Weak Infeed
=
Enabled
.
With the parameter
FCT Weak Infeed
(address
2501
) it is determined whether the
device shall trip during a weak infeed condition or not. With the setting
ECHO and
TRIP
both the echo function and the weak infeed tripping function are activated. With
the setting
ECHO only
the echo function for provision of the release signal at the in-
feeding line end is activated. There is however no tripping at the line end with missing
or weak infeed condition. As the weak-infeed measures are dependent on the signal
reception from the opposite line end, they only make sense if the protection is coordi-
nated with teleprotection (refer to Section 6.6 and/or 6.8).
The receive signal is a functional component of the trip condition. Accordingly, the
weak infeed tripping function must not be used with the blocking schemes. It is only
permissible with the permissive schemes and the comparison schemes with release
signals. In all other cases it must be switched off in address
2501
OFF
. In such cases
it is better to disable this function from the onset by selecting the setting in address
0125
to
Disabled
, during the device configuration. The associated parameters are
then not accessible.
The undervoltage setting value
UNDERVOLTAGE
(address
2505
) must in any event be
set below the minimum expected operational phase–earth voltage. The lower limit for
this setting is given by the maximum expected voltage drop at the relay location on the
weak-infeed side during a short-circuit on the protected feeder for which the distance
protection may no longer pick up.
The remaining settings apply to the echo function and are described in the corre-
sponding sections (6.6.2 and/or 6.8.2).
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...