Control During Operation
7-56
7SA6 Manual
C53000-G1176-C156-2
7.4.6
Switching Authority
Switching authority determines the command sources that are permitted for control.
From the
DeviceFront
In devices with graphic display the switching authority is determined by the upper key-
operated switch. If the key-operated switch is in horizontal position (local), the local
control is admitted via the device panel. If it is in vertical position (remote), the remote
control is admitted.
Otherwise use the device control menu: with a device ready for operation, first press
the
key. The
MAIN MENU
appears.
Using the
key, select the menu item
Control
and move to editing the control func-
tions with the
key. The selection
CONTROL
appears.
Here, select the menu item
Control Auth.
with the
key and switch to the next
selection using the
key. The selection
CONTROL AUTH.
appears (see Figure 7-57).
Figure 7-57
Setting Switching Authority with the Operator Control Panel
Pressing the
key opens a selection window in which the options
LOCAL/REMOTE
are offered.
Choose the desired option using the
and
keys, and confirm with the
key.
Acknowledge the subsequent message pressing the
key.
Use the
key to return to the
SWITCH AUTH
level; the
key to return to the
MAIN
MENU
.
From PC with
DIGSI
®
4
For safety reasons, switching authority can only be changed locally using the keypad
on the front panel of the device. Switching authority cannot be changed with DIGSI
®
4.
To perform control with DIGSI
®
4, switching authority at the device must be set to
RE-
MOTE
, or the test conditions for remote control of switching authority must not be set
to active. Switching authority is first transferred to DIGSI
®
4 when the control window
(see Figure 7-51) is opened.
MENU
CONTROL 04/05
--------------------
>
Interlock
–> 3
>
Control Auth.
–> 4
CONTROL AUTH.
--------------------
Switch Auth.> Local
ENTER
PW Unlock Control?
=-------
Enter password No. 2 (for non-interlocked
switching) and acknowledge with
ENTER
ENTER
CONTRO
------
>
Remote -----
Switc Local Local
ENTER
ENTER
ENTER
MENU
:
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...