Functions
6-321
7SA6 Manual
C53000-G1176-C156-2
es. For the device the messages designated with
*)
are displayed in the event logs, for
DIGSI
®
4 they appear in spontaneous messages.
The “plus” appearing in the message is a confirmation of the command execution: the
command execution was as expected, in other words positive. The “minus” is a neg-
ative confirmation, the command was rejected. Figure 6-158 shows the messages re-
lating to command execution and operation response information for a successful op-
eration of the circuit breaker.
The check of interlocking can be programmed separately for all switching devices and
tags that were set with a tagging command. Other internal commands such as manual
entry or abort are not checked, i.e. carried out independent of the interlocking.
Figure 6-158 Example of a message when closing the circuit breaker Q0
Standard
Interlocking
The standard interlocking includes the checks for each device which were set during
the configuration of inputs and outputs, see Section 5.2.4 under “Binary Outputs for
Switching Devices”.
An overview for processing the interlocking conditions in the relay is shown by Figure
6-159.
Table 6-20
types of command and messages
Type of command
Abbrev.
Message
Control issued
CO
CO+/–
Manual tagging (positive / negative)
MT
MT+/–
Input blocking
IB
IB+/– *)
Output blocking
OB
OB+/– *)
Control abortion
CA
CA+/–
EVENT LOG
---------------------
19.06.99 11:52:05,625
Q0 CO+ close
19.06.99 11:52:06,134
Q0 FB+ close
Содержание siprotec 7SA6
Страница 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Страница 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Страница 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Страница 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Страница 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Страница 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Страница 559: ...Control During Operation 7 45 7SA6 Manual C53000 G1176 C156 2 Figure 7 45 Circuit breaker trip test in DIGSI 4 ...
Страница 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Страница 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Страница 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Страница 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...