WARNINGS AND CAUTIONS
•
TO AVOID FIRE, SHOCK OR DEATH; TURN OFF POWER
AT CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are not sure about any part of these instructions, consult an electrician.
• Read material thoroughly before attempting to assemble and install this device or product.
• Incorrect assembly or installation may result in fire, electrical property damage, shock, personal injury, or death.
3420-009
3420-035
Maximum DC
Operating Voltage:
9.0VDC
35VDC
Clamping Voltage
@ 10 Amps:
81V
115V
Maximum Surge Current: 1kA
Strike Breakdown Voltage:
100V/micro second
100V/S
3420-009:
13V
10.5
3420-035:
48.6V
40.8V
Maximum Capacitance A-B Lines:
L-L: 2.2 pf, L-G: 73 pf
Operating Temperature Range:
-40°C to 60°C
Storage Temperature Range:
-40°C to 90°C
Relative Humidity:
0 to 95% non-condensing
Altitude:
-1000 ft. to 15000 ft.
Tested to UL 497B
Solid state semi-conductor SPD circuitry for Loop Circuit protection (Line to Line protection and both Line 1 and Line 2 to
Ground).The SPD’s enclosure is a non-conductive ABS case. ABS is a flame retardant thermoplastic, compliant with UL
497B polymeric material test requirements.
SURGE PROTECTIVE DEVICE
4-20 mA CURRENT LOOP MODULE
Cat. No. 3420-009, 3420-035
DI-000-03420-00F
ENGLISH
INSTALLATION INSTRUCTIONS
DESCRIPTION
SPECIFICATIONS
SYSTEM VOLTAGE REQUIREMENTS
Leviton’s Current Loop Modules, Cat. No. 3420-009 and 3420-035 are designed as
the primary line of protection from data line impulses and transients. The Loop Circuit
Modules are connected in series as a Surge Protective Device (SPD) in the data line.
Surge Protection Devices (SPDs) are intended for use in Current Loop Circuit applications. The voltage for
Cat. No. 3420- 009 SPD’s ranges from -9.0 to +9.0 VDC with a maximum continuous operating voltage of
9.2VDC. The voltage for Cat. No. 3420-035 SPD’s ranges from -35 to +35VDC with a maximum continuous
operating voltage of 38.5VDC.
1
1
1
2
2
2
S
H
S
hield
1
2
S
hield
Loop Circuit
M
odule
Current
S
ource
4-20
S
ystem
M
odule
Input
Output
Figure 1 - Terminal Connections
Brass Terminal Plate
Connected To Ground
Braided Ground Wire
3-Pin
Headers (2)
3-Pin Terminal
Connectors
(2 Included)
Retaining
S
crews
Figure 2 - Connector Locations
LOAD
LOAD
LOAD
+
+
+
+
+
-
-
-
-
-
CIRCUIT
CURRENT
S
OURCE
CONTROLLER
+
-
Figure 3 - Typical
M
odule Locations
Note: Insert Loop Circuit
M
odule at any one
of the locations marked “X”.