Basic Functions
176
7.13.2
Square Reduction V/F Pattern Operation
Square reduction V/F pattern is ideal for loads such as fans and pumps. It provides non-linear
acceleration and deceleration patterns to sustain torque throughout the entire frequency
range.
Group Code
Name
LCD Display
Parameter Setting
Setting Range Unit
BAS
07
V/F pattern
V/F Pattern
1
Square
0
–
3
-
3
Square2
Square Reduction V/F pattern Operation - Setting Details
Code
Description
BAS-07 V/F
Pattern
Sets the parameter value to “1
(Square)” or “2
(Square2)”
depending on the
load’s start characteristics.
Setting
Function
1
Square
The inverter produces an output voltage proportionate to
1.5 square of the operation frequency.
3
Square2
The inverter produces an output voltage proportionate to
2 square of the operation frequency. This setup is ideal for
variable torque loads, such as fans or pumps.