Using Protection Features
338
10.2.5
Speed Command Loss
When setting the operation speed using an analog input at the terminal block, communication
options, or the keypad, the speed command loss setting can be used to select the inverter
operation for situations when the speed command is lost due to the disconnection of signal
cables.
Group
Code
LCD Display
Parameter Setting
Setting Range
Unit
PRT
12
Lost Cmd Mode 1
Free-Run
-
-
13
Lost Cmd Time
-
1.0
0.0
–
120
Sec
14
Lost Preset F
-
0.00
Starting Freq
–
Max. Freq
Hz
15
AI Lost Level
1
Half of X1
-
-
OUT
31
–
33
Relay1,2, Q1
13 Lost Command -
-
Speed Command Loss Setting Details
Code
Description
PRT-12 Lost Cmd
Mode
In situations when speed commands are lost, the inverter can be
configured to operate in a specific mode:
Setting
Function
0 None
The speed command immediately becomes the
operation frequency without any protection function.
1 Free-Run
The inverter blocks output. The motor performs in
free-run condition.
2 Dec
The motor decelerates and then stops at the time set
at PRT-07 (Trip Dec Time).
3 Hold Input
The inverter calculates the average input value for 10
seconds before the loss of the speed command and
uses it as the speed reference.
4 Hold
Output
The inverter calculates the average output value for
10 seconds before the loss of the speed command
and uses it as the speed reference.
5 Lost Preset The inverter operates at the frequency set at PRT-14
(Lost Preset F).
PRT-15 AI Lost Level,
PRT-13 Lost Cmd
Time
Configure the voltage and decision time for speed command loss when
using analog input.
Setting
Function
0 Half of x1
Based on the values set at IN-08 and IN-12, a
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...