![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 161](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801161.webp)
Basic Functions
144
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
05
V1 input monitor
V1 Monitor
0.00
0.00
–
10.00 V
V
06
V1 polarity options
V1 Polarity
1
Bipolar
0
–
1
-
12
V1 minimum input
voltage
V1- volt x1
0.00
0.00
–
10.00 V
V
13
V1 output at
minimum voltage (%)
V1- Perc y1
0.00
-100.00
–
0.00% %
14
V1 maximum input
voltage
V1- Volt x2
-10.00
-10.00
–
0.00 V
V
15
V1 output at
maximum voltage (%)
V1- Perc y2
-100.00
-100.00
–
0.00% %
Rotational Directions for Different Voltage Inputs
Command /
Voltage Input
Input voltage
0
–
10 V
-10
–
0 V
FWD
Forward
Reverse
REV
Reverse
Forward
10
–
10 V Voltage Input Setting Details
Code
Description
IN-12 V1- volt x1
–
IN-15 V1- Perc y2
Sets the gradient level and offset value of the output frequency in relation to
the input voltage. These codes are displayed only when IN-
06 is set to “1
(bipolar)”.
As an example, if the minimum input voltage (at V1) is set to “
-
2 (V)” with 10%
output ratio, and the maximum voltage is set to “
-
8 (V)” with
an 80% output
ratio, the output frequency will vary within the range of 6
–
48 Hz.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...