Learning Advanced Features
Adv
anc
ed
Feat
ur
es
209
8.5
Safe Operation Mode
When the multi-function terminals are configured to operate in Safe mode, operation
commands can be entered in Safe mode only. Safe mode is used to safely control the inverter
through the multi-function terminals.
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
ADV
70
Safe operation
selection
Run En Mode
1
DI
Dependent
Always Enable /
DI Dependent
-
71
Safe operation
stop mode
Run Dis Stop
0
Free-Run
0
–
2
-
72
Safe operation
deceleration
time
Q-Stop Time
5.0
0.0
–
600.0
sec
IN
65
–
75
Px terminal
configuration
Px Define(Px: P1
–
P8
[optional: P9
–
P11])
13 RUN Enable 0
–
51
-
Safe Operation Mode Setting Details
Code
Description
IN-65
–
75 Px Define
From the multi-function terminals, select a terminal to operate in Safe mode
and set it to “1
3
(RUN Enable)”.
ADV-70 Run En
Mode
Setting
Function
0 Always Enable Safe operation mode is deactivated.
1 DI Dependent
Recognizes the operation command from a multi-
function input terminal.
ADV-71 Run Dis
Stop
Set the operation of the inverter when the multi-function input terminal
configured for Safe mode is off.
When the Safe mode signal is given, the inverter decelerates according to the
settings at the Q-Stop time. The inverter decelerates and stops according to
the deceleration time (Dec Time) settings if the run command is off.
Setting
Function
1 Free-Run
Blocks the inverter output when the multi-function
terminal is off.
2 Q-Stop
The deceleration time (Q-Stop Time) used in Safe
mode. It stops after deceleration and then the
operation can resume only when the operation
command is entered again. The operation will not
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...