Using Monitor Functions
306
9.3
Analog output
9.3.1
Voltage Output (0
–
10 V)
Select the items to be output from AO1 (Analog Output 1) terminal of the inverter terminal
block and adjust the output sizes.
Group
Code
LCD Display
Parameter Setting
Unit
OUT
01
AO1 Mode
0
Frequency
-
02
AO1 Gain
-
100.0
%
03
AO1 Bias
-
0.0
%
04
AO1 Filter
-
5
ms
05
AO1 Const %
-
0.0
%
06
AO1 Monitor
-
0.0
%
Voltage Output Setting Details
Code
Description
OUT-01 AO1
Mode
Select the output types.
Setting
Description
0
Frequency
Outputs an operation frequency as the standard. A 10 V
output is supplied based on the frequency set at DRV-20
(Max Freq).
1
Output
Current
A 10 V output is supplied from 200% of the inverter-rated
current (based on CT: Constant Torque).
2
Output
Voltage
Sets the outputs based on the inverter output voltage. A 10
V output is supplied from the voltage set at BAS-15 (Rated V).
If 0 V is set at BAS-15, 200 V/400 V models output 10 V based
on the actual input voltage (220 V and 440 V respectively).
3
DC Link
Volt
Outputs the inverter DC link voltage as the standard.
Outputs 10 V when the DC link voltage is 410 VDC for 200 V
models, and 820 VDC for 400 V models.
4
Torque
Outputs the generated torque as the standard. Outputs 10 V
at 250% of the motor-rated torque.
5
Output
Power
Monitors the output wattage. 200% of the rated output is
the maximum display voltage (10 V).
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...