Learning Advanced Features
216
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
20
PID reference
source
PID Ref Source 0
Keypad
0
–
10
-
21
PID feedback
source
PID F/B source 0
V1
0
–
9
-
22
PID proportional
gain
PID P-Gain
-
50.0
0
–
1000
%
23
PID integral time
PID I-Time
-
10.0
0
–
200.0
sec
24
PID differential
time
PID D-Time
-
0
0
–
1000
ms
25
PID feed forward
gain
PID F-Gain
-
0.0
0
–
1000
%
26
PID proportional
gain scale
P Gain Scale
-
100.0
0
–
100
%
27
PID output filter
PID Out LPF
-
0
0
–
10000
ms
28
PID mode options PID Mode
0
0
Process
PID
0-1
-
29
PID output upper
limit
PID Limit Hi
-
60.00
APP-30 setting
value
–
300
Hz
30
PID output lower
limit
PID Limit Lo
-
-60.00
-300
–
APP-029
setting value
Hz
31
PID output
inversion
PID Out Inv
-
0 No
0
–
1
-
32
PID output scale
PID Out Scale
-
100.0
0.1
–
1000
%
34
Pre-PID start
frequency
Pre-PID Freq
-
0.00
0
–
Max. Freq
Hz
35
Feedback value to
end Pre-PID
operation
Pre-PID Exit
-
0.0
0
–
100
%
36
Pre-PID delay time Pre-PID Delay
-
600
0
–
9999
sec
37
PID sleep delay
time
PID Sleep DT
-
60.0
0
–
999.9
sec
38
PID sleep
frequency
PID Sleep Freq -
0.00
0
–
Max. Freq.
Hz
39
PID wakeup level
PID WakeUp
-
35
0
–
100
%
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...